What's New
View | 2008 | 2007 | 2006 | 2005 | 2004
JULY 05 - PARTNERS IN INNOVATION REPORT ON IMPROVED THERMAL AND MOISTURE PERFORMANCE OF PITCHED ROOFS NOW AVAILABLE
Introduction
The Partners in Innovation project that was set up in
September 2001 to investigate matters concerning improved
thermal and moisture performance of pitched roofs has
now published its report. The work principally concerned
itself with investigating 'cold' pitched roofs, i.e.
those with insulation on a horizontal ceiling with an
accessible loft above. There were two reasons for this:
1. the issues surrounding cold pitched
roofs were complex and controversial and therefore demanded
an considerable degree of study;
2. the large amount of work carried out
in other countries, especially at the University of Leuven
in Belgium, on 'warm' pitched roofs, meant that they
were well understood and any further work would be in
danger of reinventing the wheel.
A range of work was done during the project which is
summarised below;
East Kilbride Test Rig
Two sets of four roofs were monitored in detail over
the winters of 2001 - 2002 and 2002 - 2003. In the first
winter, a comparison of a conventional ventilated 1F
felt roof with three variants of 'unventilated' roofs
with low resitance underlays (Tyvek 2001B Pro, with
a quoted vapour resistance 0.16 MNs/g) and different
combinations of counterbattens and batten space ventilation,
demonstrated small differences between the systems, The
rafter moisture contents in one of the roofs, with lapped
but not taped Tyvek, were consistently higher that the
others, but within safe limits; this roof was also more
prone to condensation. The air tightness of the four
roofs was not measured at this stage.
A more detailed study in the second winter compared
the ventilated roof with 1F underlay with roofs with
Tyvek 2001B Pro as before and two combinations of Roofshield,
which is air permeable and has a quoted vapour resistance
of 0.09 MNs/g. In both winters, it was found to be extremely
difficult to eliminate airflows into the 'unventilated'
roofs, a reduction of loft ventilation rate to between
12% and 30% of the fully ventilated loft, was the best
achievable. Regression analysis of the results from 2002
-2003 allowed the four roofs to be compared under standard
environmental conditions and demonstrated that the risk
of problems was not very different between the four roofs,
with some small differences in performance:
The ventilated roof with impermeable
underlay was marginally colder with slightly higher relative
humidities than the unventilated roofs with permeable
membranes.
The theoretical risk of condensation,
as predicted from the difference between the measured
loft dewpoint and underlay temperature, was lower in
the 'unventilated' roofs with LR underlays, with a resistance
0.16 MN.s/g or less, compared to the ventilated loft
with the HR underlay and the LR underlay with a resistance
of 0.09MNs/g, which was also air permeable.
Although the theoretical risk of condensation
was higher in the roofs with air permeable LR underlays
and with the impermeable HR underlay, compared to that
in the roof with air impermeable LR underlay, the actual
incidence of condensation was less. This is consistent
with air permeability or ventilation giving additional
protection against condensation
Reports of condensation
Over the winter of 2002 - 2003, there were a number
of complaints of condensation in the lofts of newly completed
houses, with an LR underlay and no designed ventilation.
Although complaints of condensation is an imprecise,
subjective measure, the number of complaints received
on each day, was strongly associated with the daily minimum
temperature, with a peak of complaints during a cold
spell when minimum temperatures fell below -4°C for
a number of days.
Drying of houses
It is assumed that the extra moisture load caused by 'wet'
materials drying out in new houses, leads to an increased
risk of condensation in the loft. Wet trades will impose
some extra moisture load on houses; however there is
little evidence of the size of this effect. The moisture
produced within a house by the normal activities of the
occupants can vary from 5 kg/day for a pensioner living
alone, up to 20 kg/day for a family with a number of
small children. If the drying of the fabric adds something
of the order of 1 - 2 kg/day to this, it may not be important,
however, if it adds 5 - 10 kg/day it is obviously highly
important. Data is needed on the actual rates of evaporation
in new houses.
Air leakage though roof coverings
At the start of the PiI project it was assumed that
air ingress through many tiling systems would be so limited
that it would be necessary to install dedicated batten
space ventilators, if an LR membrane was used with an
unventilated loft. The default situation, reflected in
BS5250:2002, was 'you must install batten space ventilators
unless you have evidence that the tiles/slates are very
air open'. Quantitative pressurisation tests and qualitative
smoke tests carried out in a number of roofs have both
demonstrated substantial air leakage though all the tiling
systems tested. It is now felt that the situation can
be summed up as : 'It can be assumed that most natural
slating and tiling systems are sufficiently air open,
unless there is evidence that they are air tight. Fibre
cement slates, metal tiles or sheet coverings would be
considered insufficiently air open''. It has been possible
to define an objective test for air openness of tiling
systems based on BS5534, Annex L, but with equipment
to measure flows down to 2Pa.
Air leakage around loft hatches
Tests of air leakage around five commercially available
loft hatches, all marketed as air tight, showed a variation
of 50 to 1 between the best and worst hatches, with no
guidance available to aid designers/builders which is
the appropriate one to choose.
Energy Saving
One of the justifications for the use of 'unventilated'
lofts with LR underlays is the potential energy savings
from restricting ventilation in the loft. Claims have
been made up to 25% energy saving. The evidence for this
comes from some research done in Finland and one pair
of houses at BRE Garston; the data from the latter was
inconclusive in cold weather. One study of cold roof
performance in Finland showed an energy saving
of 1 - 2 % when loft ventilation was eliminated. When
air was sucked down from the loft into the house, using
the ceiling insulation as a heat exchanger, much greater
savings results, however this is hardly a realistic situation.
A simplified steady state model, which uses the air
flow equations developed for RoofCond (see below), has
been developed to assess the parameters that affect heat
flows and energy use houses as the parameters of the
roof are changed. This suggests that it is more likely
that any savings will come from improving the airtightness
of the ceiling than from reducing air flows through the
loft.
RoofCond Software
The software package RoofCond that was developed during
the course of the project was designed to carry out sensitivity
analysis of the factors that effect condensation in cold
pitched roofs. Further work is needed to validate its
use; in particular it should be compared with measured
data in buildings. However when used for sensitivity
analysis the following points can be regarded as reasonably
robust:
Lower ventilation rates are needed in
a LR roof to give the same level of protection from condensation
as in a fully ventilated HR roof, all other parameters
being equal.
As a comparative sensitivity analysis
tool it can be used to compare the condensation risk
of a conventionally ventilated roof with a HR underlay
directly with a roof with an LR underlay.
As the ventilation in the loft is reduced,
the condensate peak rises with both underlay types.
As leakage through the ceiling is reduced,
the condensate peak falls with both underlay types.
As the vapour resistance of an underlay
is reduced below 0.25 MNs/g, the condensate peak falls.
Addition of ridge ventilators lowers
the condensation peak.
All these trends can be considered to be representative
of the performance of roofs in practice.
Click
here to download the full Pii report PDF >
Back >
© 2008
Glidevale Ltd. |